Error : Hot water securing
If the error 102 message is displayed on the AC•THOR /AC•THOR 9s , this means that the hot water securing function is active, but no temperature sensor has been connected or activated yet.
To correct this error, connect the sensor to the AC•THOR and activate it via the display.
To do this, click on settings (gearwheel symbol), scroll to the item "sensors" and select it.
You will then see the serial number of the connected sensor and its current temperature on the display. Click once on this line. Now the sensor number is displayed to the right of the displayed temperature. This sensor is now active. Finally, save the setting.
TIP: If the optional temperature safeguard is not used, the heat generator has a thermostat and you only want to use excess energy anyway, then the installation of the temperature sensor is not necessary at all!
Our "Support" section offers many useful practical tips that will help you install and commission our solutions.
Furthermore, you will learn about all the most important innovations of my-PV products.
More articles
Referencia
New feed-in regulations in the Netherlands require a rethink
A Dutch homeowner minimizes feed-in fees by utilizing surplus PV energy to heat water.
Leer más...Empresa
SOL•THOR wins German Design Award 2025
The DC Power Manager SOL •THOR has received the German Design Award in the category “Excellent Product Design”.
Leer más...General
Minimizing feed-in costs in the Netherlands
The Netherlands introduced a fee for feeding electricity into the grid. Fees can be reduced by increasing self-consumption.
Leer más...