Error : Hot water securing

If the error 102 message is displayed on the AC•THOR /AC•THOR 9s , this means that the hot water securing function is active, but no temperature sensor has been connected or activated yet.

To correct this error, connect the sensor to the AC•THOR and activate it via the display.

To do this, click on settings (gearwheel symbol), scroll to the item "sensors" and select it.

You will then see the serial number of the connected sensor and its current temperature on the display. Click once on this line. Now the sensor number is displayed to the right of the displayed temperature. This sensor is now active. Finally, save the setting.

TIP: If the optional temperature safeguard is not used, the heat generator has a thermostat and you only want to use excess energy anyway, then the installation of the temperature sensor is not necessary at all!

Our "Support" section offers many useful practical tips that will help you install and commission our solutions.

Furthermore, you will learn about all the most important innovations of my-PV products.

More articles

Two men holding a certificate stand in a room with solar equipment and a sign that reads "Empowering the Solar Future."

Empresa

my-PV recertificado según ISO 9001:2015

En 2026, my-PV fue una vez más recertificado exitosamente según ISO 9001:2015.

Leer más...
Modern house with solar panels on the roof and an outdoor heat pump unit, surrounded by a grassy yard under a clear blue sky.

General

Protege tu bomba de calor y aumenta el autoconsumo con calor fotovoltaico real.

La combinación de una bomba de calor modulante y calefacción directa solar-eléctrica con el AC•THOR reduce ...

Leer más...
A two-story building with solar panels on the roof, featuring large windows and a red roof. A person walks by in the foreground.

Referencia

Agua caliente para un internado en Kenia

Durante años, los 50 niños se ducharon con agua fría. Ahora, my-PV ofrece calefacción autónoma.

Leer más...