Error : Hot water securing

If the error 102 message is displayed on the AC•THOR /AC•THOR 9s , this means that the hot water securing function is active, but no temperature sensor has been connected or activated yet.

To correct this error, connect the sensor to the AC•THOR and activate it via the display.

To do this, click on settings (gearwheel symbol), scroll to the item "sensors" and select it.

You will then see the serial number of the connected sensor and its current temperature on the display. Click once on this line. Now the sensor number is displayed to the right of the displayed temperature. This sensor is now active. Finally, save the setting.

TIP: If the optional temperature safeguard is not used, the heat generator has a thermostat and you only want to use excess energy anyway, then the installation of the temperature sensor is not necessary at all!

Our "Support" section offers many useful practical tips that will help you install and commission our solutions.

Furthermore, you will learn about all the most important innovations of my-PV products.

More articles

Aerial view of my-PV building with solar panels on roof and facade, visible logo, and cars in the parking lot.

L'entreprise

Activation du noyau en béton dans le bâtiment de l'entreprise - Rapport annuel 2024

Notre bâtiment solaire-électrique : 3e année, coûts élevés mais performance assurée

lire la suite...
House in France with rooftop solar panels, overlooking a coastal town and the sea in the background.

Généralités

Nouvelle réduction de TVA : boostez l’autoconsommation photovoltaïque en France

À partir d’octobre 2025, la France appliquera une TVA réduite de 5,5 % sur les installations PV résidentielles jusqu’à 9 kW.

lire la suite...

Partenaires

Nouveau partenaire de compatibilité : Haier Energy

Les solutions my-PV sont désormais compatibles avec les onduleurs et les systèmes de stockage de Haier Energy.

lire la suite...